Application

Used as interconnecting cable for measuring, controlling or regulation in control equipment for assembly and production lines, conveyors and for computer units. Suitable for fixed installations or for flexible use in conditions of light mechanical stress. Can be used outdoors when protected, and in dry or moist conditions indoors. used in home appliances and power tools.

Technical Data

Operating temp.: -10 °C to 70 °C
Voltage Grade up to: 1.1 kV
Requirement of oxygen in air to catch fire: more then 29.5%
Temperature required to catch fire (with 21% oxygen):  more then 250 °C
Visibility during cable burning: less then 30%

“RADIX” copper conductor, PVC insulated and sheathed multicore flexible cables

Size / Area in Sq.mm. No. & size of wire Nominal Insulation thickness (mm) Overall core Diameter (mm) Sheath thickness (mm) Overall diameter (mm) Max. resistance @20°C (ohm/km) Current rating (Amp.)
2 core 3 core 4 core 2 core 3 core 4 core
0.50 16/0.20 0.60 2.20 0.90 0.90 0.90 6.20 6.60 7.20 39.00 4.00
0.75 24/0.20 0.60 2.50 0.90 0.90 0.90 6.80 7.20 7.90 26.00 7.00
1.00 32/0.20 0.60 2.60 0.90 0.90 0.90 7.00 7.50 8.10 19.50 11.00
1.50 48/0.20 0.60 2.90 0.90 0.90 1.00 7.60 8.10 9.00 13.30 14.00
2.50 80/0.20 0.70 3.50 1.00 1.00 1.00 9.00 9.60 10.50 7.98 19.00
4.00 56/0.30 0.80 4.30 1.00 1.00 1.00 10.60 11.30 12.40 4.95 25.00
6.00 84/0.30 0.80 5.50 1.30 1.30 1.40 13.70 14.00 16.50 3.30 32.00
10.00 140/0.30 1.00 6.70 1.40 1.40 1.40 16.50 18.00 19.00 1.91 45.00
16.00 224/0.30 1.00 8.40 1.40 1.40 1.40 19.00 20.50 23.00 1.21 60.00

 

Note: Insulation thickness, sheath thickness and overall dimension given in the table are nominal values. The number of wires and strand diameter are satisfy the requirements of conductor resistance as per IS:8130/1984. As per to IS :694/2010

“RADIX” copper conductor, PVC insulated and sheathed multicore flexible control cables

Size in sq. mm. Size in mm. Current Rating Approximate overall diameter of cable (mm)
5 core 6 core  7 core 8 core 10 core 12 core 14 core 16 core 19 core
0.50 16/0.20 4.00 8.30 8.50 8.50 9.30 10.80 11.20 12.00 12.60 13.20
0.75 24/0.20 7.00 9.10 9.50 9.50 10.40 12.20 12.60 13.30 14.20 14.90
1.00 32/0.20 11.00 9.60 9.80 9.80 10.70 12.60 13.00 13.70 14.60 15.60
1.50 48/0.20 14.00 10.30 10.70 10.70 11.90 13.80 14.30 15.20 16.00 17.10
2.50 80/0.20 19.00 11.70 12.70 12.70 14.10 16.60 17.20 18.10 19.30 20.30
4.00 56/0.30 25.00 13.95 15.30 15.30 16.90 20.20 20.70 21.80 23.20 24.50

 

Note: Insulation thickness, sheath thickness and overall dimension given in the table are nominal values. The number of wires and strand diameter are satisfy the requirements of conductor resistance as per IS:8130/1984. As per to IS :694/201

Silent Features
  • High flexibility & Durability ensures long life
  • Excellent resistant to moisture,abrasion, Oil & grease
  • Excellent elctrical & mechanical property
  • Standerd packing : 90 m & 100 m
  • Core colour as per IS : 694 : 2010 2 core : Red,Black , 3 core : Red,Black,Green , 4 core : Red, Yellow, Blue, Green
  • Available Sheath colours : Black, White, Grey, Orange

Note: On special request FRLS insulated cables can also be manufactured.

Cable Standards

CONDUCTOR

99.9% pure electrolytic flexible bare copper conductor
As per IS : 8130

INSULATION

PVC Insulation Type – D
As per IS : 5831

OUTER SHEATH

PVC Sheath Type : ST-3
As per IS : 5831

CABLE STANDERD

IS : 694 : 2010, BS 6500